Parameterization¶
The arrangement of the parameter data is performed with Control Builder Plus software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
| Name | Value | Internal Value  | 
Internal value, Type  | 
Default | Min. | Max. | EDS Slot Index | 
|---|---|---|---|---|---|---|---|
| Module ID | Internal | 6520 *1) | WORD | 0x1978 | 0 | 65535 | xx01 | 
| Ignore module | No Yes  | 
0 1  | 
BYTE | No 0x00  | 
|||
| Parameter length | Internal | 8 | BYTE | 0 | 0 | 255 | xx02 *2) | 
| Check Supply | Off On  | 
0 1 | BYTE | On 0x01  | 
|||
| Analog Data Format | Default | 0 | BYTE | Default 0x00  | 
*1) with CS31 and addresses less than 70, the value is increased by 1
*2) Value is hexadecimal: HighByte is slot (xx: 0 … 7), LowByte is index (1 … n)
| GSD file: | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) =  | 
0x0B 0x79, 0x19, 0x08, \ 0x01, 0x00, \ 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00;  |