Technical Data of the Analog Inputs

Number of channels per module 4 individually configurable voltage or current inputs
Distribution of channels into groups 1 (4 channels per group)
Resolution  
  Unipolar

Voltage: 0 V … +5 V; 0 V … + 10 V: 12 bits

Current 0 mA … 20 mA; 4 mA … 20 mA: 12 bits

  Bipolar Voltage -2.5 V … +2.5 V; -5 V … +5 V: 11 bits plus sign
Connection of the signals I0- to I3- Terminals 3, 6, 9, 12
Connection of the signals I0+ to I3+ Terminals 2, 5, 8, 11
Input type Differential
Electrical isolation No electrical isolation between the inputs and the I/O-Bus
Common mode input range Signal voltage plus common mode voltage must be within ±12 V
Indication of the input signals No
Channel input resistance Voltage: >1 MW, current: ca. 250 W
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

0.5 % of full scale (voltage)

0.5 % of full scale (current 0…20 mA)

0.7 % of full scale (current 4…20 mA)

at 25°C

Max.

2 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Time constant of the input filter Voltage: 300 µs, current: 300 µs
Relationship between input signal and hex code Table Measuring Ranges Analog Input/Output Module AX561
Analog to digital conversion time Typ. 500 µs per channel
Unused inputs Can be left open and should be configured as “unused”
Overvoltage protection Yes, up to 30 V DC only for voltage input
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m