Number of channels per module |
2 configurable voltage or current outputs |
Distribution of channels into groups |
1 (2 channels per group) |
Connection of the signals O0U- and O1U+ |
Terminals 13 and 15 |
Connection of the signals O0I+ and O1I+ |
Terminals 14 and 16 |
Output type |
Bipolar with voltage, unipolar with current |
Resolution |
12 bits or 11 bits plus sign |
Accuracy |
|
|
Typical (25 °C) |
±0.5 % of full scale |
|
Worst case (at 0 … 60 °C or EMC disturbances) |
±2 % of full scale |
Indication of the output signals |
No |
Output Resistance (load) as current output |
0 … 500 W |
Output load ability as voltage output |
2 mA max. |
Relationship between input signal and hex code |
Table Output Ranges Analog Input/Output Module AX561 |
Unused inputs |
Can be left open and should be configured as “unused” |
Overvoltage protection |
Yes, up to 30 V DC |
Max. cable length (conductor cross section > 0,14 mm²) |
|
|
Unshielded wire |
10 m |
|
Shielded wire |
100 m |