Technical Data of the Analog Outputs

Number of channels per module 2 configurable voltage or current outputs
Distribution of channels into groups 1 (2 channels per group)
Connection of the signals O0U- and O1U+ Terminals 13 and 15
Connection of the signals O0I+ and O1I+ Terminals 14 and 16
Output type Bipolar with voltage, unipolar with current
Resolution 12 bits or 11 bits plus sign
Accuracy  
  Typical (25 °C) ±0.5 % of full scale
  Worst case (at 0 … 60 °C or EMC disturbances) ±2 % of full scale
Indication of the output signals No
Output Resistance (load) as current output 0 … 500 W
Output load ability as voltage output 2 mA max.
Relationship between input signal and hex code Table Output Ranges Analog Input/Output Module AX561
Unused inputs Can be left open and should be configured as “unused”
Overvoltage protection Yes, up to 30 V DC
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m