2000hex…2FFFhex - Interface Error¶
DEC | HEX | Error description |
---|---|---|
8193 | 2001 | Invalid interface, Communication Module number or slot ID COM: Interface is not configured in the “free mode” HA: Wrong COM number at input COM |
8194 | 2002 | Command not supported by the interface. The function is not supported by the device firmware. Block library newer than the device firmware. |
8195 | 2003 | Invalid interface or Communication Module type. Block is not suitable for this type. |
8197 | 2005 | HA..: CS31 Bus failure |
8211 | 2013 | Timeout COM_MOD_MAST: Slave did not respond within the specified time HA..: No Ethernet link, No DPRAM communication |
8212 | 2014 | Framing error (incorrect baud rate, number of stop bits and/or bits per character) |
8213 | 2015 | Parity error HA: Remote CS31 Slave sync error / Digital/Analog IO buffer difference |
8214 | 2016 | Idle error COM..: Character timeout occurred |
8215 | 2017 | Invalid length COM_MOD_MAST: Invalid data length received COM_REC: Received more data than expected |
8216 | 2018 | Checksum error |
8217 | 2019 | Handshake error |
8218 | 201A | Service failed COM_REC: Unknown error message of the interface COM_SET_PROT: Interface hardware not accessible. Initialization already failed during system start-up. COM_MOD_SLV_SET_ADDR..: Internal error (e.g. wrong return value of internal function, null pointer received) CS31..: Internal error (e.g. CS31 communication failed) FC..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in config found) HA..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in config found) |
8219 | 201B | Access error HA..: Remote CPU CS31 Bus failure IO..: Module number does not exist |
8220 | 201C | Incorrect number (quantity) COM_SET_PROT: Invalid protocol index. Index is not supported by the device firmware. COM_MOD_SLV_SET_ADDR..: Invalid protocol index. HA..: Different number of CS31 Slaves on line A and line B IO..: Invalid module number |
8223 | 201F | Access denied COM..: Access to the interface is not possible at present. Control Builder, SYCON.net, OPC or another program is logged in via the interface. |
8226 | 2022 | COM_MOD_SLV_SET_ADDR..: Wrong configuration (No protocols configured). FC..: Wrong configuration (e.g. no ABB Control Builder Plus configuration, no CS31 configured, no CS31 modules found). HA..: Sync table full or values different. |
8234 | 202A | HA: Configuration error:
|
8299 | 2029 | HA..: Wrong configuration (e.g. no CS31 configured, no CS31 Bus Modules found, CS31 of line A and line B swapped) |