2000hex…2FFFhex - Interface Error

DEC HEX Error description
8193 2001

Invalid interface, Communication Module number or slot ID

COM: Interface is not configured in the “free mode”

HA: Wrong COM number at input COM

8194 2002 Command not supported by the interface. The function is not supported by the device firmware. Block library newer than the device firmware.
8195 2003 Invalid interface or Communication Module type. Block is not suitable for this type.
8197 2005 HA..: CS31 Bus failure
8211 2013

Timeout

COM_MOD_MAST: Slave did not respond within the specified time

HA..: No Ethernet link, No DPRAM communication

8212 2014 Framing error (incorrect baud rate, number of stop bits and/or bits per character)
8213 2015

Parity error

HA: Remote CS31 Slave sync error / Digital/Analog IO buffer difference

8214 2016

Idle error

COM..: Character timeout occurred

8215 2017

Invalid length

COM_MOD_MAST: Invalid data length received

COM_REC: Received more data than expected

8216 2018 Checksum error
8217 2019 Handshake error
8218 201A

Service failed

COM_REC: Unknown error message of the interface

COM_SET_PROT: Interface hardware not accessible. Initialization already failed during system start-up.

COM_MOD_SLV_SET_ADDR..: Internal error (e.g. wrong return value of internal function, null pointer received)

CS31..: Internal error (e.g. CS31 communication failed)

FC..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in config found)

HA..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in config found)

8219 201B

Access error

HA..: Remote CPU CS31 Bus failure

IO..: Module number does not exist

8220 201C

Incorrect number (quantity)

COM_SET_PROT: Invalid protocol index. Index is not supported by the device firmware.

COM_MOD_SLV_SET_ADDR..: Invalid protocol index.

HA..: Different number of CS31 Slaves on line A and line B

IO..: Invalid module number

8223 201F

Access denied

COM..: Access to the interface is not possible at present. Control Builder, SYCON.net, OPC or another program is logged in via the interface.

8226 2022

COM_MOD_SLV_SET_ADDR..: Wrong configuration (No protocols configured).

FC..: Wrong configuration (e.g. no ABB Control Builder Plus configuration, no CS31 configured, no CS31 modules found).

HA..: Sync table full or values different.

8234 202A

HA: Configuration error:

  • Wrong CM574-RS communication
  • CM574-RS COM interface is not configured for shared communication
  • CM574-RS not added to Communication Module slot
  • Wrong configuration of DIAG blocks
8299 2029 HA..: Wrong configuration (e.g. no CS31 configured, no CS31 Bus Modules found, CS31 of line A and line B swapped)