Features

Transmission technique

  • RS485, potential separated, insulation voltage up to 850 V.
  • Twisted pair cable or optical fibre as a medium for the bus.
  • Up to 32 subscribers (master and slave modules) without repeaters and up to 126 subscribers on one bus with repeaters.
  • Integrated repeater controller.

Communication

  • Up to 244 bytes of input data and 244 bytes of output data per slave, 2944 I/O points max.
  • Cyclic user data transfer between DP master and DP slave.
  • Acyclic data transfer from master to master.
  • Slave configuration check.
  • Efficient diagnosis functions, 3 graduated diagnosis messaging levels.
  • Synchronization of inputs and/or outputs via control commands.

Protection functions

  • Message transfer with Hamming distance HD = 4.
  • Errors during data transfer are detected by the CRC check and cause a repetition of the telegram.
  • Access protection for inputs and outputs of the slaves.
  • Incorrect parameter settings are avoided since bus subscribers with faulty parameters are not included in the user data operation.
  • A failure of a bus subscriber is registered in the master and indicated via a common diagnosis.

Status indication

Status indivation via 4 LEDs

Standardization

  • EN 50170
  • DIN 19245 part 1
  • DIN 19245 part 3
  • DPV1

Terms, Definitions and Abbreviations

PROFIBUS® DP PROcess FIeldBUS - Decentral Periphery
DPM1 DP master (class 1), normal bus master
DPM2 DP master (class 2), commissioning device
DPS DP slave, I/O module
GSD Modules master data
DPV1 Guideline for functional expansions of PROFIBUS® DP
PNO PROFIBUS Nutzer Organisation (PROFIBUS® user organization)