As of CBP 2.4:¶
For Modbus TCP/IP protocol configuration add a new object for Modbus Server settings under Ethernet Interface. In the device tree double-click the new added item to open the configuration:
The following parameters are available:
Parameter | Default | Value | Meaning | Generic see remark 1 |
---|---|---|---|---|
Disable write to %MB0.x from | 0 | 0…65535 | Disable write access for segment 0 starting at %MB0.x | Disable write to %MB0.x from |
Disable write to %MB0.x to | 0 | 0…65535 | Disable write access for segment 0 up to %MB0.x | Disable write to %MB0.x to |
Disable read to %MB0.x from | 0 | 0…65535 | Disable read access for segment 0 starting at %MB0.x | Disable read to %MB0.x from |
Disable read to %MB0.x to | 0 | 0…65535 | Disable read access for segment 0 up to %MB0.x | Disable read to %MB0.x to |
Disable write to %MB1.x from | 0 | 0…65535 | Disable write access for segment 1 starting at %MB1.x | Disable write to %MB1.x from |
Disable write to %MB1.x to | 0 | 0…65535 | Disable write access for segment 1 up to %MB1.x | Disable write to %MB1.x to |
Disable read to %MB1.x from | 0 | 0…65535 | Disable read access for segment 1 starting at %MB1.x | Disable read to %MB1.x from |
Disable read to %MB1.x to | 0 | 0…65535 | Disable write access for segment 1 up at %MB1.x | Disable read to %MB1.x to |
Remark 1: Generic device configuration view parameters
Tab IP Settings Configuration or Modbus TCP/IP Server Configuration shows a list of all available parameters which is only visible if the parameter Show generic device configuration views is activated (open Options dialog window with menu item Tools -> Options, parameter is located under section Device editor):