LED Status Display

The LEDs are located at the front of module. There are 2 different groups:

  • The 5 system LEDs (PWR, STA1 ETH, STA2 ETH, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
  • The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs:
LED Color OFF ON Flashing
PWR/RUN green Process supply voltage missing Internal supply voltage OK, module ready for communication with IO Controller Start-up / preparing communication
yellow — — —
STA1 ETH (System-LED “BF”) green — Device configured, cyclic data exchange running —
red — — Device is not configured
STA2 ETH (System-LED “SF”) green — — Got identification request from IO Controller
red No system error System error (collective error) —
S-ERR red No error Internal error –
I/O-Bus green No expansion modules connected or communication error Expansion modules connected and operational —
ETH1 green No connection at Ethernet interface Connected to Ethernet interface —
yellow — Device is transmitting telegrams Device is transmitting telegrams
ETH2 green No connection at Ethernet interface Connected to Ethernet interface —
yellow — Device is transmitting telegrams Device is transmitting telegrams
Status of the 29 process LEDs:
LED Color OFF ON Flashing
DC0 to DC7 yellow Input/Output is OFF Input/Output is ON –
DI8 to DI15 yellow Input is OFF Input is ON (the input voltage is even displayed if the supply voltage is OFF) –
DO8 to DO15 yellow Output is OFF Output is ON –
UP green Process supply voltage missing Process supply voltage OK and initialization finished –
UP3 green Process supply voltage missing Process supply voltage OK –
CH-ERR1 to CH-ERR3 red No error or process supply voltage missing Internal error Error on one channel of the corresponding group