Mounting of S500-eCo I/O Modules on a Metal PlateΒΆ

Note

One TA566 Wall Mounting Accessory TA566 Wall Mounting Accessory is needed per S500-eCo I/O Module.

Attention

:strong:Risk of function faults!

The S500-eCo I/O Modules are earthed via the metal plate.

The I/O-Modules must only be mount to a metal plate with metal screws. No isolating washers must be used. The metal plate must be included into the earthing conception of the plant.

  1. 1. Snap in the TA566 at the back side of the I/O-Module (see illustration below).

  2. 2. Push the IO Module with the hands against other I/O-Modules or an AC500-CPU. The I/O-Bus is connected automatically.

  3. 3. Fix the I/O-Module with two screws (max. diameter: 4 mm) to the metal plate.