DPM_SLV_DIAG

../_images/0d0765d9e38ad9250a33139000eba54e
Parameter Value
Library_File_Name PROFIBUS_AC500_V25.lib
Firmware V2.5
Type Type_Function_Block_History
Group Diagnosis

The Function Block DPM_SLV_DIAG implements the PROFIBUS DP function DDLM_Slave_Diag.

Every time a FALSE → TRUE edge is applied to input EN, DPM_SLV_DIAG reads the data at its inputs and sends a corresponding request message to the Communication Module. Further FALSE → TRUE edges at input EN are ignored until the processing of the active requests is finished.

The completion of the request processing is indicated by DONE = TRUE.