Diagnosis

In cases of short circuit or overload, the digital outputs are turned off. The modules performs reactivation automatically. Thus an acknowledgement of the errors is not necessary. The error message is stored via the LED.

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500-Display <− Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser

Byte 6

Bit 6..7

- Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

PNIO diagnosis block
Class Interface Device Module Channel

Error-

Identifier

Error message Remedy
  *1) *2) *3) *4)      
Module errors CI592-CS31
3 11 ADR 31 31 19 Checksum error in the I/O module Replace I/O module
3 11 ADR 31 31 3 Timeout in the I/O module
3 11 ADR 31 31 40 Different hard-/firmware versions in the module
3 11 ADR 31 31 43 Internal error in the module
3 11 ADR 31 31 36 Internal data exchange failure
3 11 ADR 31 31 9 Overflow diagnosis buffer Restart
3 11 ADR 31 31 26 Parameter error Check Master
3 11 ADR 31 31 11 Process voltage UP too low Check process supply voltage
3 11 ADR 31/1..7 31 17 No communication with I/O device Replace I/O module
3 11 ADR 1..7 31 32 Wrong I/O device type on socket Replace I/O module / Check configuration
4 11 ADR 31 31 45 Process voltage UP OFF Turn process voltage ON
4 11 ADR 1..7 31 31 At least one module does not support failsafe function Check modules and parameterization
4 11 ADR 31/1..7 31 34 No response during initialization of the I/O module Replace I/O module
Channel error digital CI592-CS31
4 11 31 31/1..7 14..21   *5) 47 Short circuit at digital output Check terminals
Channel error analog CI592-CS31
4 11 31 31/1..7 8..11   *6) 48 Analog value overflow or broken wire at an analog input Check value or check terminals
4 11 31 31/1..7 8..11   *6) 7 Analog value underflow at an analog input Check value
4 11 31 31/1..7 8..11   *6) 47 Short-circuit at an analog input Check terminals
4 11 31 31/1..7 12..13   *7) 4 Analog value overflow at an analog output Check output value
4 11 31 31/1..7 12..13   *7) 7 Analog value underflow at an analog output Check output value

Remarks:

*1)

In AC500 the following interface identifier applies:

14 = I/O-Bus,  11 = COM1 (e.g. CS31 bus), 12 = COM2.

The FBP diagnosis block does not contain this identifier.

*2)

With “Device” the following allocation applies:

31 = Module itself, 1..7 = Expansion module 1..7, ADR = Hardware address (e.g. of the DC551)

*3)

With “Module” the following allocation applies:

31 = Module itself; 1..7 = Expansion 1..7

*4) In case of module errors, with channel “31 = Module itself” is output.
*5) Ch = 14..21 indicates the digital inputs/outputs DC8..DC15
*6) Ch = 8..11 indicates the analog inputs AI0..AI3
*7) Ch = 12..13 indicates the analog outputs AO0..AO1