Connection of analog output loads (current)

The following figure shows the connection of output loads to the analog output AO0. Proceed with the analog output AO1 in the same way.

../_images/56e3fba93b09f36b0a3313900154ac911

Connection of analog output loads (current)

The following measuring ranges can be configured CS31 Bus Module CI592-CS31 with Digital and Analog Inputs and Outputs CS31 Bus Module CI592-CS31 with Digital and Analog Inputs and Outputs :

Current 0…20 mA Load 0…500 Ω 1 channel used
Current 4…20 mA Load 0…500 Ω 1 channel used

The function of the LEDs is described under Diagnosis and Displays / Displays.

Unused analog outputs can be left open-circuited.