Parameters of the Module - if used without fast counter¶
Name | Value | Internal Value |
Internal Value, type |
Default |
---|---|---|---|---|
Module ID *1) | Internal | 2726 | WORD | 2726 |
Parameter length | Internal | 23 | BYTE | 23 |
Error LED / Failsafe function *2) | On | 0 | BYTE | 0 |
Off by E4 | 1 | |||
Off by E3 | 3 | |||
On + failsafe | 16 | |||
Off by E4 + failsafe | 17 | |||
Off by E3 + failsafe | 19 | |||
Check supply | off | 0 | BYTE | |
on | 1 | 1 |
*1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission
*2) | Setting | Meaning |
---|---|---|
On | Error-LED lights up at errors of all error classes, Failsafe-mode off | |
Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode off | |
Off by E3 | Error LED lights up at errors of error classes E1 and E2, Failsafe-mode off | |
On +Failsafe | Error-LED lights up at errors of all error classes, Failsafe-mode on* | |
Off by E4 + Failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode on* | |
Off by E3 + Failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafe-mode on* |
*) The parameters behaviourAOatCommunicationFault and behaviourDOatCommunicationFault are only analyzed if the Failsafe-mode is ON.