Parameters of the Module - if used with fast counter¶
| Name | Value | Internal Value |
Internal Value, type | Default |
| Module ID *1) | Internal | 2725 | WORD | 2725 |
| Parameter length | Internal | 22 | BYTE | 22 |
| Error LED / Failsafe function *2) | On | 0 | BYTE | 0 |
| Off by E4 | 1 | |||
| Off by E3 | 3 | |||
| On + failsafe | 16 | |||
| Off by E4 + failsafe | 17 | |||
| Off by E3 + failsafe | 19 | |||
| Check supply | off | 0 | BYTE | |
| on | 1 | 1 |
Note
If a DC551 is configured as a Fast Counter module and ‘0 - no Counter’ in the Control Builder Plus is selected the channel ERR LEDs stays on and the module does not start up. The address was adjusted with ‘71’.
Only the‘0- no Counter’ mode does not operate. If any other counter is selected e.g. ‘1-1 Up counter’ the module starts up and can be utilized.