Technical Data of the Module

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process supply voltage  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V)
  Protection against reverse voltage Yes
  Rated protection fuse at UP 10 A fast
  Rated value 24 V DC
  Max. ripple 5 %
Current consumption  
  From UP 0.07 A + max. 0.5 A per output
  From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module Ca. 5 mA
  Inrush current from UP (at power-up) 0.04 A²s
Interface RS485
Protocol CS31
Terminals of the Bus Line 1 1.3 and 1.5
Terminals of the Bus Line 2 1.4 and 1.6
Electrical isolation Yes, CS31 Bus from the rest of the module
Max. power dissipation within the module 6 W (outputs unloaded)
Weight (without Terminal Unit) ca. 125 g
Mounting position Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels are protected against reverse polarity, reverse supply, short circuit and continuous overvoltages up to 30 V DC.