Technical Data of the Module¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Process supply voltage | ||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V) | |
Protection against reverse voltage | Yes | |
Rated protection fuse at UP | 10 A fast | |
Rated value | 24 V DC | |
Max. ripple | 5 % | |
Current consumption | ||
From UP | 0.07 A + max. 0.5 A per output | |
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 5 mA | |
Inrush current from UP (at power-up) | 0.04 A²s | |
Interface | RS485 | |
Protocol | CS31 | |
Terminals of the Bus Line 1 | 1.3 and 1.5 | |
Terminals of the Bus Line 2 | 1.4 and 1.6 | |
Electrical isolation | Yes, CS31 Bus from the rest of the module | |
Max. power dissipation within the module | 6 W (outputs unloaded) | |
Weight (without Terminal Unit) | ca. 125 g | |
Mounting position | Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C) | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note
All I/O channels are protected against reverse polarity, reverse supply, short circuit and continuous overvoltages up to 30 V DC.