Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Number of channels per module 24
Distribution of the channels into groups 3 groups of 8 channels each (2.0…2.7, 3.0…3.7, 4.0…4.7), the allocation of the channels is given by the inserted CS31 Bus Module
CS31 field bus connector Terminals 1.0 to 1.7
Rated voltage 24 V DC
Max. permitted total current 10 A (between the terminals 1.8…4.8 and 1.9…4.9)
Earthing Direct connection to the earthed DIN rail or via the screws with wall mounting
 
Screw-type terminals  
Type Front terminal, conductor connection vertically with respect to the printed circuit board
For details See Connection System Connection System
   
Spring terminals  
Type Front terminal, conductor connection vertically with respect to the printed circuit board
For details See Connection System Connection System
 
Dimensions  
Width x height x depth 67.5 x 135 x 30 mm
Weight 200 g
Mounting position Horizontal or vertical