Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Number of I/O channels per module Max. 24 (depending on the inserted Bus Module)
Distribution of the channels into groups 3 groups of max. 8 channels each (2.0 … 2.7, 3.0 … 3.7, 4.0 … 4.7), the allocation of the channels is given by the inserted Bus Module
Network interface connector 9-pole D-SUB connector, female
Rated voltage 24 V DC
Max. permitted total current 10 A via the supply terminals (UP, UP3 and ZP)
Earthing Direct connection to the earthed DIN rail or via the screws with wall mounting
 
Screw-type terminals  
Type Front terminal, conductor connection vertically with respect to the printed circuit board
For details See Connection System Connection System
 
Spring terminals  
Type Front terminal, conductor connection vertically with respect to the printed circuit board
For details See Connection System Connection System
 
Dimensions  
Width x height x depth 67.5 x 135 x 30 mm
Weight 200 g
Mounting position Horizontal or vertical