Parametrization

Arrangement of parameter data is performed by your master configuration software Automation Builder.

Caution

:strong:Risk of configuration errors!

Contradictory parameter settings may cause configuration errors of the CI590-CS31-HA and attached I/O modules. Please make sure, the high-speed counter mode is not set to value 0 if the module is included with high-speed counters in PLC configuration.

The parameter data directly influences module functionality.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Name Value Internal Value Internal Value, Type Default Min. Max.
Module address 1 2740 * BYTE

2740

0 x 0AB4

0 61
Ignore module

No

Yes

0

1

BYTE No (0 x 00) - -
Parameter length Internal

8

7 **

BYTE

8

7 **

0 255
Check supply

Off

On

0

1

BYTE

On

0 x 01

- -
Error LED / Failsafe Function

On

Off by E4

Off by E3

On + Failsafe

Off by E4 + Failsafe

Off by E3 + Failsafe

- - On - -
Stop behavior

Switch over

Stop

Both stop/failsafe

0

1

2

BYTE 0 - -
Output compare

No check

Binary

Analog ± 256

Analog ± 512

Binary + Analog 256

Binary + Analog 512

0

1

2

3

4

5

BYTE 0 - -
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

8 ms

0 x 02

- -
Fast counter

0

:

10 ***

0

:

10

BYTE

Mode 0

0 x 00

- -
Detection short-circuit at outputs

Off

On

0

1

BYTE

On

0 x 01

- -
Behavior outputs at communication fault

Off

Last value

Substitute value

0

1

2

BYTE

Off

0 x 00

- -
Substitute value 0…65535 0…0xffff WORD 0 - -

* with CS31 and addresses less than 70 and FBP, the value is increased by 1.

** with CS31 and addresses less than 70, without the parameter “High-speed counter”.

*** Counter operating modes, see description of the high-speed counter.