Complete Error List of the S500 I/O Modules

E1..E4 d1 d2 d3 d4 Identifier 000…063 AC500 display <- displayed in 5)
Class Comp Dev Mod Ch Err PS501 PLC Browser
Byte 6 Bit 6..7 - Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

FBP diagnosis block
Class Interface Device Module Channel Error identifier Error message Remedy Online number Online text
 
   
Errors of the S500 I/O Modules
S500 I/O Module errors
Light errors
3 14 1..10 1 0..7 4 Measurement overflow at the I/O module Check channel wiring and sensor power supply 234881028 E3: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549380 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
3 14 1..10 31 31 3 Timeout in the I/O Module Replace I/O module 234946499 E3: I/O-Bus, Mod. [1..10]
11 / 12 ADR 1..10 184549379 E3: COM [1|2] [PROTOCOL] [ADR], [1..10], (>=)31
3 14 1..10 31 31 9 Overflow diagnosis buffer Restart 234946505 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549385 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 10 Process voltage too high Check process voltage 234946506 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 11 Process voltage too low Check process voltage 234946507 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549387 E3: COM [1|2] [PROTOCOL] [ADR] [1.. 10], (>=) 31
3 14 1..10 31 31 18 Plausibility check failed (iParameter) Check configuration 234946514 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 19 Checksum error in the I/O Module

Non-safety I/O: Replace I/O Module

Safety-I/O: Check safety configuration and CRCs for iParameters and F-Parameters

234946515 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549395 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=) 31
3 14 1..10 31 31 20 PROFIsafe communication error Restart I/O Module. If this error persists, contact ABB technical support. 234946516 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 25 PROFIsafe watchdog timed out Restart I/O Module. If this error persists, increase PROFIsafe watchdog time. 234946521 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 26 Parameter value Check master or configuration 234946522 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549402 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 28 F-Parameter configuration and address switch value do not match Check I/O Module’s F-Parameter configuration and module address switch value 234946524 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 36 Internal data interchange disturbed Replace I/O Module 234946532 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549412 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 40 Different hardware and firmware versions in the module Replace I/O Module 234946536 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549416 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 43 Internal error in the device Replace I/O Module 234946539 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549419 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 47 Sensor voltage too low Check sensor voltage 234946543 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549423 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
Warnings
4 14 1..10 31 31 45

Process voltage switched off

(ON->OFF)

Process voltage ON 234946541 E4: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549421 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
Channel errors of the S500 I/O modules
Warnings
4 14 1..10 1 0..7 1 Wrong measurement; wrong temperature at the compensations channel Check temperature compensation channel 234881025 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549376 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 2

AI531: Wrong measurement; potential difference is to high

CD522: PWM duty cycle out of duty area

AI531: Check potential difference

CD522: Check min/max values

234881026 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549378 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 4 Measurement overflow at the I/O module Check channel wiring and sensor power supply 234881028 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549380 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 7 Measurement underflow at the analog input Check input value 234881031 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549383 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 4 1..10 1 0..7 10 Input/output value to high Check input/output value 234881034 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549386 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 11

AI531:Output voltage 10 V to small

CD522: Output voltage 5 V to small (sensor)

AI531: Check charge of the output voltage

CD522: Check connection

234881035 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549387 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 18 Internal fuse to 0 V blown, 0 V not connected to ZP Replace I/O Module 234881042 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 /12 ADR 1..10 184549394 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 47 Short-circuit at the analog input Check terminal 234881071 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549423 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10, [0..7]
4 14 1..10 1 0..7 48 Measurement overflow or cut wire at the analog input Check input value and terminal 234881072 E4: I/O-Bus, Mod. [1..7], 1, [0..7]
11 / 12 ADR 1..10 184549424 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 2 0..23 47 Short-circuit at the digital output Check terminal 234881071 E4: I/O-Bus, Mod. [1.. 10], 2, [0..7]
11 / 12 ADR 1..10 184549423 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 3 0..7 48 Measurement overflow at the analog output Check output value 234881072 E4: I/O-Bus, Mod. [1.. 10], 3, [0..7]
11 / 12 ADR 1..10 184549424 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 3 0..7 7 Measurement underflow at the analog output Check output value 234881031 E4: I/O-Bus, Mod. [1.. 10], 3, [0..7]
Module errors DC551-CS31 and CI590
Light errors
3 11 ADR 31 31 3 Timeout in the I/O Module Replace I/O Module 184614851 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 9 Overflow of diagnosis buffer Restart 184614857 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 11 Process voltage too low Check process voltage 184614859 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 1..7 31 17 No communication with the I/O Module Replace I/O Module 184549393 E3: COM1 [PROTOCOL] [ADR], [1..7], (>=)31
3 11 ADR 31 31 19 Checksum error in the I/O Module Replace I/O Module 184614867 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 26 Parameter error Check master 184614874 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 28 Configuration of PLC 1 and PLC 2 are different Check PLC CS31 Module configuration 184614876 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 36 Internal data interchange disturbed Check PLC program 184614884 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 40 Different hardware and firmware versions in the module Replace I/O Module 184614888 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 43 Internal error in the module Replace I/O Module 184614891 E3: COM1 [PROTOCOL] [ADR]
Warnings
4 11 ADR 31 31 33 PLC conflict *1 Check PLC program 184614881 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 34 Outputs are different (synchronization error) *2 Check PLC program and synchronize 184614882 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 45 Process voltage ON/OFF Process voltage ON 184614893 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 32 Wrong I/O Module on the slot Replace I/O Module and check configuration 184614882 E4: COM1 [PROTOCOL] [ADR], [1..7], (>=)31
1..10 184549410 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 34 No response during initialization of the I/O Module Replace I/O Module 184614880 E4: COM1 [PROTOCOL] [ADR]
1..10 184549408 E4: COM1 [PROTOCOL] [ADR], [1..7], (>=)31

*1) FB HA control mode is both primary or both secondary. Could be only an error output of FB if too much diagnosis

*2) if no other error occurs, the programs are not identical and parameter is set to report an error in this case

Channel errors DC551-CS31 and CI590
Warnings
4 11 ADR 31/1..10 8..23 47 Short-circuit at the digital output Check terminal 184549423 E4: COM1 [PROTOCOL] [ADR] E4: COM1 [PROTOCOL] [ADR], [1..7], (>=)31
Module errors DC505-FBP
Light errors
3 - 1..7 31 31 11 Process voltage too low Check process voltage    
3 - 1..7 31 31 17 No communication with the I/O module Replace I/O Module    
3 - 31 31 31 3 Timeout in the I/O module    
3 - 31 31 31 9 Overflow of diagnosis buffer Restart    
3 - 31 31 31 19 Checksum error in the I/O module Replace I/O Module    
3 - 31 31 31 26 Parameter error Check master    
3 - 31 31 31 36 Internal data interchange disturbed Replace I/O Module    
3 - 31 31 31 40 Different hardware and firmware versions in the module    
3 - 31 31 31 43 Internal error in the module    
Warnings
4 - 31 31 31 45 Process voltage ON/OFF Process voltage ON    
4 - 31/1..7 31 31 32 Wrong I/O Module on the slot Replace I/O Module and check configuration    
4 - 31/1..7 31 31 34 No response during initialization of the I/O module Replace I/O Module    
Channel errors DC505-FBP
Warnings
4 - 31 2 8..15 47 Short-circuit at the digital output Check terminal    
Parameter errors
Light errors
3 14 1..10 31 3 1 Wrong parameter value Check configuration 234944705  
3 14 1..10 31 3 28 F-Parameter configuration and address switch value do not match Check I/O Module F-Parameter configuration and module address switch value 234944732 E3: I/O-Bus, Mod. 1
3 14 1..10 31 3 19 Checksum error has occured in iParameter or F-Parameters Check safety configuration and CRCs for iParameter and F-Parameters 234944723 E3: I/O-Bus, Mod. 1
Runtime errors
Light errors
3 14 1..10 31 2 3 PROFIsafe watchdog timed out Restart I/O Module. If this error persists, increase PROFIsafe watchdog time 234944643 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 19 Checksum error has occured in iParameters Restart I/O Module. If this error persists, replace I/O module. Contact ABB technical support 234944659 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 20 PROFIsafe communication error Restart I/O Module. If this error persists, contact ABB technical support 234944660 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 28 Internal error Contact ABB technical support. Replace I/O Module 234944668 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 43 Internal runtime error in I/O module Contact ABB technical support. Replace I/O module 234944683 E3: I/O-Bus, Mod. 1
Background test errors
Light errors
3 14 1..10 31 2 4 I/O Module overvoltage Check I/O module power supply 234944644 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 7 I/O Module undervoltage Check I/O module power supply 234944647 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 18 Internal error Restart I/O module. If this error persists, replace I/O module. Contact ABB technical support 234944658 E3: I/O-Bus, Mod. 1
Specific errors AI, DI and DO
Light errors
3 14 1..10 0 0..15 3 Discrepancy time expired Check discrepancy time value, channel wiring and sensor 234881027 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 0 0..15 12

Module 0:

Test pulse error

Check wiring and sensor 234881036 E3: I/O-Bus, Mod. 1-10, 0, 0-15
2 0..8

Module 2:

Channel stuck-at error

Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. E3: I/O-Bus, Mod. 1..10, 2, 0..8
3 14 1..10 0 0..15 13

Module 0:

Channel test pulse cross-talk error

Check wiring and sensor. If this error persists, replace I/O Module. Contact ABB technical support 234881037 E3: I/O-Bus, Mod. 1-10, 0, 0-15
2 0..8

Module 2:

Channel readback error

Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. E3: I/O-Bus, Mod. 1..10, 2, 0..8
3 14 1..10 0 0..15 18 Channel test error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881042 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 0 0..15 25 Channel stuck - at error Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. 234881049 E3: I/O-Bus, Mod. 1..10, 0, 0..15
3 14 1..10 0 0..15 28 Channel cross-talk error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881052 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 1 0..3 4 Measurement overflow at the I/O Module Check channel wiring and sensor power supply 234881028 E3: I/O-Bus, Mod. 1..10, 1, 0..3
3 14 1..10 1 0..3 7 Measurement underflow at the I/O Module Check channel wiring and sensor power supply 234881031 E3: I/O-Bus, Mod. 1..10, 1, 0..3
3 14 1..10 1 0..3 45 Cut wire Check channel wiring and sensor power supply 234881069 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 1 0..3 51 Overload Check channel wiring and sensor power supply 234881075 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 1 0..3 55 Channel value difference too high Adjust tolerance window for channels. Check channel wiring and sensor configuration. 234881079 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 2 0..8 18 Channel cross-talk error Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. 234881042 E3: I/O-Bus, Mod. 1..10, 4, 0..8
3 14 1..10 2 0..8 43 Internal error Contact ABB technical support. Replace I/O Module. 234881067 E3: I/O-Bus, Mod. 1, 4, 0-7
3 14 1..10 4 0..7 13 Channel test error Check I/O module wiring. Restart I/O Module, if needed. If this error persists, replace I/O module 234881037 E3: I/O-Bus, Mod. 1, 4, 0-7
3 14 1..10 4 0..7 17 Channel test error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881025 E3: I/O-Bus, Mod. 1, 4, 0-7
Notes
 

AC500 uses the following interface identification:

14 = I/O Bus, 11 = COM1 (e.g., CS31 Bus), 12 = COM2

FBP diagnosis blocks do not contain this identifier.

 

The assignment for “Device” is as follows:

31 = Module, 1..10 = Expansion 1..10

 

The assignment for “Module” is as follows:

31 = Module or module type (1=AI, 2=DO, 3=AO, 4=DC)

 
In case of module errors, “31 = Module” is reported for the channel.
 
In the current AC500 CPU firmware version, errors reported to the AC500 CPU by the DC505-FBP cannot be directly made visible on the display or in the PLC Browser of the Control Builder PS501.