Technical Data of the Digital OutputsΒΆ

Number of channels per module 8 triac outputs
Distribution of the channels into groups 8 groups (1 channel per group)
Connection of the channels O0 to O7 Terminals 1, 3, 5, 7, 10, 12, 14, 16
Reference potential for the channels O0 to O7 Terminals 2, 4, 6, 8, 11, 13, 15, 17
Output voltage for signal 1 On Request
Max. leakage current with signal 0 1.1 mA rms at 132 V AC and 1.8 mA rms at 264 V AC
Output voltage  
Rated value 120 V AC or 240 V AC
Indication of the output signals 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered through the I/O-Bus
Way of operation Non-latching type
Output delay  
0 to 1 On Request
1 to 0 On Request
Output current  
Rated current per channel (max.) 0.3 A
Rated current per group (max.) 0.3 A
Surge current (max.) On request
Lamp load (max.) On request
Spark suppression with inductive AC loads Must be performed externally according to driven load specification
Switching Frequencies  
With resistive loads Max. 10 Hz
With inductive loads Not applicable
With lamp loads Max. 10 Hz
Short circuit / Overload proof No, should be provided by an external fuse or circuit breaker
Rated protection fuse 2 A fast
Overload message No
Output current limitation No
Resistance to feedback against 230 V AC No
Connection of 2 outputs in parallel Not applicable
Max. cable length  
Shielded 500 m
Unshielded 150 m