Number of channels per module |
8 triac outputs |
Distribution of the channels into groups |
8 groups (1 channel per group) |
Connection of the channels O0 to O7 |
Terminals 1, 3, 5, 7, 10, 12, 14, 16 |
Reference potential for the channels O0 to O7 |
Terminals 2, 4, 6, 8, 11, 13, 15, 17 |
Output voltage for signal 1 |
On Request |
Max. leakage current with signal 0 |
1.1 mA rms at 132 V AC and 1.8 mA rms at 264 V AC |
Output voltage |
|
Rated value |
120 V AC or 240 V AC |
Indication of the output signals |
1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered through the I/O-Bus |
Way of operation |
Non-latching type |
Output delay |
|
0 to 1 |
On Request |
1 to 0 |
On Request |
Output current |
|
Rated current per channel (max.) |
0.3 A |
Rated current per group (max.) |
0.3 A |
Surge current (max.) |
On request |
Lamp load (max.) |
On request |
Spark suppression with inductive AC loads |
Must be performed externally according to driven load specification |
Switching Frequencies |
|
With resistive loads |
Max. 10 Hz |
With inductive loads |
Not applicable |
With lamp loads |
Max. 10 Hz |
Short circuit / Overload proof |
No, should be provided by an external fuse or circuit breaker |
Rated protection fuse |
2 A fast |
Overload message |
No |
Output current limitation |
No |
Resistance to feedback against 230 V AC |
No |
Connection of 2 outputs in parallel |
Not applicable |
Max. cable length |
|
Shielded |
500 m |
Unshielded |
150 m |