Technical Data of the Analog \ Outputs¶
| Number of channels per module | 2 | |
| Distribution of channels into groups | 1 group for 2 channels | |
| Connection of the channels AO0+…AO1+ | Terminals 3.5 and 3.6 | |
| Reference potential for AO0+ to AO1+ | Terminal 3.7 (AO-) for voltage output Terminals 1.9, 2.9, 3.9 and 4.9 for current output |
|
| Output type | ||
| Unipolar | Current | |
| Bipolar | Voltage | |
| Electrical isolation | Against internal supply and other modules | |
| Configurability | -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually) | |
Output resistance (load), as current output |
0…500 W | |
Output loadability, as voltage output |
±10 mA max. | |
| Indication of the output signals | 1 LED per channel (brightness depends on the value of the analog signal) | |
| Resolution | 12 bits (+ sign) | |
| Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. 0.5 %, max. 1 % | |
| Relationship between input signal and hex code | See Output Ranges Voltage and Current Digital/Analog Input/Output Module DA501 | |
| Unused outputs | Are configured as “unused” (default value) and can be left open-circuited | |