Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is 0necessary to adapt the parameters to your system configuration.

Module slot address: Y = 1…7

Name Value

Internal

Value

Internal

Value, type

Default EDS Slot / Index
Module ID *1) Internal 1810 WORD 1810 0x0Y01
Ignore module *2) Internal

Yes

No

BYTE No not for FBP
Parameter length Internal 8 BYTE 8 0xY02
Check supply off 0 BYTE   0xY03
on 1 1  
Fast counter *4)

0

:

10 *3)

0

:

10

BYTE 0 not for FBP
   
Behaviour outputs at comm. error *5)

Off Last value Last value 5 sec Last value 10 sec Substitute value

Substitute value 5 sec

Substitute value 10 sec

0

1

6

11

2

7

12

BYTE

Off

0x00

0x0Y07

*1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission

*2) Not for FBP

*3) Counter operating modes Fast Counter, see description of the Fast Counter Fast Counter

*4) With FBP or CS31 without the parameter “Fast Counter”

Note

The Fast Counter of the module does not work if the module is connected to an FBP Interface Module or CS31 Bus Module.

*5) The parameter Behaviour outputs at comm. error is only analyzed if the Failsafe-mode is ON.

*2) Setting Meaning
  On Error-LED lights up at errors of all error classes, Failsafe-mode off
  Off by E4 Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode off
  Off by E3 Error LED lights up at errors of error classes E1 and E2, Failsafe-mode off
  On +Failsafe Error-LED lights up at errors of all error classes, Failsafe-mode on*
  Off by E4 + Failsafe Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode on*
  Off by E3 + Failsafe Error LED lights up at errors of error classes E1 and E2, Failsafe-mode on*