Electrical Connection¶
The Digital/Analog Input/Output Module DA501 can be connected to the following devices via the I/O-Bus connector:
- FBP Interface Module DC505-FBP
- CS31 Bus Modules, e. g. DC551-CS31, CI590 and CI592
- AC500 CPUs (PM5xx)
- other AC500-I/O-devices.
Note
Mounting, disassembling and electrical connection for the Terminal Units and the I/O modules are described in detail in S500 System Data System Data AC500.
The electrical connection is carried out by using the 40 terminals of the Terminal Unit TU515/TU516 I/O Terminal Units TU515 and TU516 for I/O Expansion Modules.
The assignment of the terminals:
Terminal | Signal | Meaning |
---|---|---|
1.0 | DI0 | Signal of the digital input DI0 |
1.1 | DI1 | Signal of the digital input DI1 |
1.2 | DI2 | Signal of the digital input DI2 |
1.3 | DI3 | Signal of the digital input DI3 |
1.4 | DI4 | Signal of the digital input DI4 |
1.5 | DI5 | Signal of the digital input DI5 |
1.6 | DI6 | Signal of the digital input DI6 |
1.7 | DI7 | Signal of the digital input DI7 |
1.8 | UP | Process voltage UP (24 V DC) |
1.9 | ZP | Process voltage ZP (0 V DC) |
2.0 | DI8 | Signal of the digital input DI8 |
2.1 | DI9 | Signal of the digital input DI9 |
2.2 | DI10 | Signal of the digital input DI10 |
2.3 | DI11 | Signal of the digital input DI11 |
2.4 | DI12 | Signal of the digital input DI12 |
2.5 | DI13 | Signal of the digital input DI13 |
2.6 | DI14 | Signal of the digital input DI14 |
2.7 | DI15 | Signal of the digital input DI15 |
2.8 | UP | Process voltage UP (24 V DC) |
2.9 | ZP | Process voltage ZP (0 V DC) |
3.0 | AI0+ | Plus pole of analog input signal 0 |
3.1 | AI1+ | Plus pole of analog input signal 1 |
3.2 | AI2+ | Plus pole of analog input signal 2 |
3.3 | AI3+ | Plus pole of analog input signal 3 |
3.4 | AI- | Minus pole of analog input signals 0 to 3 |
3.5 | AO0+ | Plus pole of analog output signal 0 |
3.6 | AO1+ | Plus pole of analog output signal 1 |
3.7 | AO- | Minus pole of analog output signals 0 and 1 |
3.8 | UP | Process voltage UP (24 V DC) |
3.9 | ZP | Process voltage ZP (0 V DC) |
4.0 | C16 | Signal of the configurable digital input/output C16 |
4.1 | C17 | Signal of the configurable digital input/output C17 |
4.2 | C18 | Signal of the configurable digital input/output C18 |
4.3 | C19 | Signal of the configurable digital input/output C19 |
4.4 | C20 | Signal of the configurable digital input/output C20 |
4.5 | C21 | Signal of the configurable digital input/output C21 |
4.6 | C22 | Signal of the configurable digital input/output C22 |
4.7 | C23 | Signal of the configurable digital input/output C23 |
4.8 | UP | Process voltage UP (24 V DC) |
4.9 | ZP | Process voltage ZP (0 V DC) |
The internal power supply voltage for the module’s circuitry is carried out via the I/O-Bus (provided by a Bus Module or a CPU). Thus, the current consumption from 24 V DC power supply at the terminals L+/UP and M/ZP of the CPU/Bus Module increases by 2 mA per DA501.
The external power supply connection is carried out via the UP (+24 V DC) and the ZP (0 V DC) terminals.
Attention
:strong:Risk of damaging the PLC modules!
The PLC modules must not be removed when the plant is powered on.
Make sure that all voltage sources (supply and process voltage) are switched off before you are removing or replacing a module.
Attention
:strong:Risk of damaging the PLC modules!
The PLC modules can be damaged by overvoltages and short circuits.
Make sure that all voltage sources (supply and process voltage) are switched off before you are beginning with operations at the system.
Caution
:strong:Risk of imprecise and faulty measurements!
Analog signals may be distorted seriously by external electromagnetic influences.
Use shielded wires when wiring analog signal sources. The cable shield must be grounded at both ends of the cable. Provide a potential equalisation of a low resistance to avoid high potential differences between different parts of the plant.
Terminal assignment of the Digital/Analog I/O module DA501
The module provides several diagnosis functions Digital/Analog Input/Output Module DA501.
- Connection of the digital inputs
- Connection of the configurable digital inputs/outputs
- Connection of resistance thermometers in 2-wire configuration to the \ analog inputs
- Connection of resistance thermometers in 3-wire configuration to the \ analog inputs
- Connection of active-type analog sensors (voltage) with electrically \ isolated power supply to the analog inputs
- Connection of active-type analog sensors (current) with electrically \ isolated power supply to the analog inputs
- Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply to the analog inputs
- Connection of passive-type analog sensors (current) to the analog inputs
- Connection of active-type analog sensors (voltage) to differential \ analog inputs
- Use of analog inputs as digital inputs
- Connection of analog output loads (voltage)
- Connection of analog output loads (current)