Technical Data of the Module¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
| Process supply voltage | ||
| Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V) | |
| Protection against reverse voltage | yes | |
| Rated protection fuse at UP | 10 A fast | |
| Rated value | 24 V DC | |
| Max. ripple | 5 % | |
| Current consumption | ||
| From UP | 0.07 A + max. 0.5 A per output | |
| From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | ca. 2 mA | |
| Inrush current from UP (at power-up) | 0.04 A:sup:2s | |
| Electrical isolation | yes, per module | |
| Max. power dissipation within the module | 6 W (outputs unloaded) | |
| Weight (without Terminal Unit) | ca. 125 g | |
| Mounting position | Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C) | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |
Note
All I/O channels are protected against reverse polarity, reverse supply, short circuit and continuous overvoltages up to 30 V DC.