Displays¶
Statuses of the LEDs:
| LED | Status | Color | LED = OFF | LED = ON | LED flashes | 
|---|---|---|---|---|---|
| PWR | Process voltage 24 V DC via terminal and process voltage via I/O-Bus | Green | CPU module voltage or external 24 V DC supply voltage is missing | I/O-Bus voltage and external 24 V DC supply voltage are present (LED is on after startup of the module (approx. 1 s)) | — | 
| ERR | Channel or module error | Red | No error or process voltage is missing | Serious error in the module | Axis related error | 
| P0…P3 | Pulse output | Yellow | Output = OFF | Output = ON | LED follows the status of the outputs, depending on frequency | 
| I0…I3 | Digital Input | Yellow | Input = OFF | Input = ON | — | 
| O0…O1 | Reserved | Yellow | — | — | — |