| Number of channels per module | 
6 transistor outputs (24 V DC, 0.5 A max.) | 
| Distribution of the channels into groups | 
1 group of 6 channels | 
| Electrical isolation | 
Yes, per group | 
| Connection of the channels DO0 to DO5 | 
Terminals 13 to 18 | 
| Common power supply voltage | 
Terminals 19 (+24 V DC, signal name UP) and 20 (0 V DC,     signal name ZP) | 
| Reference potential for the channels DO0 to DO5 | 
Terminal 20 (minus pole of the process voltage, name     ZP) | 
| Indication of the output signals | 
1 yellow LED per channel; the LED is on when the output     signal is high (signal 1) | 
| Way of operation | 
Non-latching type | 
| Min. output voltage at signal 1 | 
20 V DC at max. current consumption | 
| Output delay (max. at rated load) | 
  | 
| 0 to 1 | 
50 µs | 
| 1 to 0 | 
200 µs | 
| Rated protection fuse (per group) | 
3 A fast | 
| Output current | 
  | 
| Rated current per channel (max.) | 
0.5 A at UP 24 V DC | 
| Rated current per group (max.) | 
3 A | 
| Rated current (all channels together, max.) | 
3 A | 
| Lamp load (max.) | 
5 W | 
| Max. leakage current with signal 0 | 
0.5 mA | 
| Demagnetization when inductive loads are switched off | 
Must be performed externally according to driven load     specification | 
| Switching Frequencies | 
  | 
| With inductive loads | 
Max. 0.5 Hz | 
| With lamp loads | 
Max. 1 Hz at max. 5 W | 
| Short circuit / Overload proof | 
No | 
| Overload message | 
No | 
| Output current limitation | 
No | 
| Resistance to feedback against 24 V DC | 
No | 
| Connection of 2 outputs in parallel | 
Not possible | 
| Max. cable length | 
  | 
| Shielded | 
500 m | 
| Unshielded | 
150 m |