Electrical Connection

Attention

:strong:Risk of damaging the PLC modules!

The PLC modules must not be removed when the plant is powered on.

Make sure that all voltage sources (supply and process voltage) are switched off before you are

  • connecting or disconnecting any signal or terminal block
  • removing or replacing a module.

Attention

:strong:Risk of damaging the PLC modules!

The PLC modules can be damaged by overvoltages and short circuits.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you are beginning with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

Note

When replacing a processor module, it is recommended to mark each wire connected to the Onboard I/O terminal block before disconnecting. This should ensure to reconnect the wires in the same order.

The electrical connection is carried out by using a non-removable 20-pole Terminal Block.

The following block diagram shows the internal construction of the Onboard I/Os:

../_images/38930bf0e387e2f60a33139000eba54e1 ../_images/f6925cf7e387e2a80a33139000eba54e1
PM56x-T(P) PM56x-R(P)

Assignment of the terminals for PM56x-T(P)

Terminal Signal Meaning
1 C0..5 Input common for digital input signals DI0 to DI5
2 DI0 Digital input signal DI0
3 DI1 Digital input signal DI1
4 DI2 Digital input signal DI2
5 DI3 Digital input signal DI3
6 DI4 Digital input signal DI4
7 DI5 Digital input signal DI5
8 AI0 Analog voltage input signal AI0
9 AI1 Analog voltage input signal AI1
10 AOU Analog voltage output
11 AOI Analog current output
12 M Input/output common for analog signals
13 DO0 Digital output signal O0
14 DO1 Digital output signal O1
15 DO2 Digital output signal O2
16 DO3 Digital output signal O3
17 DO4 Digital output signal O4
18 DO5 Digital output signal O5
19 UP Process supply voltage UP +24 V DC
20 ZP Process supply voltage ZP 0 V

Assignment of the terminals for PM56x-R(P)

Terminal Signal Meaning
1 C0..5 Input common for digital input signals DI0 to DI5
2 DI0 Digital input signal DI0
3 DI1 Digital input signal DI1
4 DI2 Digital input signal DI2
5 DI3 Digital input signal DI3
6 DI4 Digital input signal DI4
7 DI5 Digital input signal DI5
8 AI0 Analog voltage input signal AI0
9 AI1 Analog voltage input signal AI1
10 AOU Analog voltage output
11 AOI Analog current output
12 M Input/output common for analog signals
13 NO0 Normally-open relay contact of the output NO0
14 NO1 Normally-open relay contact of the output NO1
15 NO2 Normally-open relay contact of the output NO2
16 R0..2 Output common for signals NO0 to NO2
17 NO3 Normally-open relay contact of the output NO3
18 NO4 Normally-open relay contact of the output NO4
19 NO5 Normally-open relay contact of the output NO5
20 R3..5 Output common for signals NO3 to NO5