Equipotential Bonding¶
- Install sufficiently dimensioned equipotential bondings, if potential differences are present or have to be expected in your application between different parts of the installation.
- The impedance of a equipotential bonding must be equal or lower than 10 % of the shield impedance of the shielded signal cables between the same points.
- The conductor cross section of a equipotential bonding must be able to withstand the maximum possible compensating current. By experience, a conductor cross section of 16 mm² has proven to be sufficient.
- Equipotential bondings and shielded signal cables should be laid close to each other. This prevents coming up inductive loops in which disturbances could be induced.
- Equipotential bondings must be connected to PE with low impedance.
AC500, equipotential bondings