Mounting and Disassembling the Processor Module PM595

Assembly on DIN rail

../_images/0dd7e697cdbac5bf0a33139007620cf8

Assembly

  1. Put the Processor Module on the DIN rail above and then snapped-in below. The disassembly is carried out in a reversed order.

../_images/fc1d3d7acdbc23b60a331390514f7711

Disassembly

  1. Pull Down the Processor Module.

  2. Remove it.

Warning

:strong:Risk of malfunctions and damages to persons!

Unused slots for Communication Modules are not protected against accidentally touch. Dust and Dirt may cause contact problems and malfunctions.

Unused slots for Communication Modules must be covered with Dummy Communication Modules (TA524 TA524 - Dummy Communication Module).

I/O-Bus connectors must not be touched during operation.

Attention

Only use TA543 accessory when the PLC is to be screw mounted. With DIN rail mounting the PLC could not be removed from the rail without the risk of damaging the housing.

Assembly with Screws

If the Processor Module should be mounted with screws, Screw Mounting Accessories TA543 TA543 - Screw Mounting Accessory must be inserted at the rear side first. These plastic parts prevent bending of the Processor Module while screwing on. 2x TA543 Screw Mounting Accessories are needed per PM595. A dimension drawing for the position of screw’s holes can be found in Mechanical Dimensions AC500 Mechanical Dimensions AC500.

../_images/a1337ce0cdbe15530a33139000cea9351

Assembly with screws for PM595

  1. Snap 2x TA543 Screw Mounting Accessories to the positions marked in the picture.

  2. Fasten the Processor Module with 4 screw (diameter 4 mm max.)

Note

By wall mounting, the Processor Module PM595 is earthed through the screws. It is necessary that

  • the screws have a conductive surface (e.g. steel zinc-plated or brass nickel-plated)
  • the mounting plate is earthed
  • the screws have a good electrical contact to the mounting plate