Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module DC523: Module slot address: Y = 1…7

Nr. Name Value

Internal

value

Internal value, type Default Min. Max.

EDS

Slot/Index

1 Module ID Internal

1215

*1)

Word

1215

0x04BF

0 65535 0x0Y01

2

*2)

Ignore module

No

Yes

0

1

Byte

No

0x00

    not for FBP
3 Parameter length Internal 9 Byte

9-CPU

8-FBP

0 255 0x0Y02
4 Check supply

Off

on

0

1

Byte

On

0x01

0 1 0x=Y03
5 Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

Byte

8 ms

0x02

0 3 0x0Y04

6

*4)

Fast counter

0

:

10 *3)

0

:

10

Byte

Mode 0

0x00

    not for FBP
7 Short-circuit detection of output or sensor supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y05
8 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y06
9

Substitute value at outputs

B23 = Output 23

Bit 0 = Output 0

0…

16777215

0…

0x00ff-ffff

DWord

0

0x0000

-0000

0 224−1 0x0Y07

*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

*3) Counter Operating Modes Fast Counter, see description of the Fast Counter Fast Counter

*4) With FBP or CS31 without the parameter Fast counter

Note

The Fast Counter of the module does not work if the module is connected to a

  • FBP Interface Module
  • CS31 Bus Module
  • CANopen Bus Module
GSD file:    
DC523:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

11

0x04, 0xc0, 0x08, \

0x01, 0x02, 0x01, 0x00, 0x00, 0x00, 0x00, 0x00;