| 4 analog TC inputs, individually configurable for | Not used (default) |
| Voltage -80 mV … + 80 mV | |
| Thermocouple J-type -210 °C … +1200 °C | |
| Thermocouple K-type -270 °C … +1372 °C | |
| Thermocouple R-type -50 °C … +1768 °C | |
| Thermocouple S-type -50 °C … +1768 °C | |
| Thermocouple T-type -270 °C … +400 °C | |
| Thermocouple E-type -270 °C … +1000 °C | |
| Thermocouple N-type -270 °C … +1300 °C |
| Resolution of the analog channels | |
| - Temperature | 0.1 °C |
| LED displays | 2 LEDs for process voltage and error messages |
| Internal supply | Via I/O-Bus |
| External supply | Via the terminals UP (process voltage 24 V DC) and ZP (0 V DC) |