Technical data of the analog inputs

Number of channels per module 4 configurable thermocouple (TC) inputs
Distribution of channels into groups 1 (4 channels per group)
Resolution  
  Temperature 0.1 °C
  Voltage 15 bits plus sign
Connection of the signals I0+ to I3+ Terminals 1, 3, 5 and 7
Connection of the signals I0- to I3- Terminals 2, 4, 6 and 8
Input type Floating thermocouple
Electrical isolation Against internal power supply and other modules
Common mode rejection > 120 dB at 120 V AC
Indication of the input signals No
Module update time All channels: < 1.6 s
Channel input resistance On Request
Input filter attenuation -3 dB at 15 kHz
Cold junction error ±1.5 °C
Basic error 0.1 % of full-scale (voltage)
Accuracy  
  Typical (at 25 °C) Depending on thermocouple, see table below
  Worst case (at 0 … 60 °C ) ±2 % of full scale (T-Type: ±3 % for -240… -270 °C)
Relationship between input signal and hex code table Analog Input Module AI563
Analog to digital conversion time 400 ms per channel
Unused inputs Can be left open and should be configured as “unused”
Overvoltage protection Yes, up to 30 V DC
Repeatability On Request
Wire loop resistance < 100 Ω
Max. cable length (conductor cross section > 0,14 mm²)  
Unshielded wire 10 m
Shielded wire 100 m