Substitute value¶
| Intended behaviour of output channel when the control system stops: | Required setting of the module parameter “Behaviour of outputs in case of a communication error” | Required setting of the channel parameter “Substitute value” |
|---|---|---|
| Output OFF | Off | 0 |
| Last value infinite | Last value | 0 |
| Last value for 5 s and then turn off | Last value 5 sec | 0 |
| Last value for 10 s and then turn off | Last value 10 sec | 0 |
| Substitute value infinite | Substitute value | depending on configuration |
| Substitute value for 5 s and then turn off | Substitute value 5 sec | depending on configuration |
| Substitute value for 10 s and then turn off | Substitute value 10 sec | depending on configuration |