Technical Data of the Relay Outputs¶
Number of channels per module | 8 relay outputs |
Distribution of channels into groups | 8 groups of 1 channel each |
Connection of the channel R0 | terminal 2.0 (common), 3.0 (NO) and 4.0 (NC) |
Connection of the channel R1 | terminal 2.1 (common), 3.1 (NO) and 4.1 (NC) |
: | : |
Connection of the channel R6 | terminal 2.6 (common), 3.6 (NO) and 4.6 (NC) |
Connection of the channel R7 | terminal 2.7 (common), 3.7 (NO) and 4.7 (NC) |
Electrical isolation | between the channels and from the rest of the module |
Indication of the output signals | one yellow LED per channel, the LED is ON when the relay coil is energized |
Output delay (0->1 or 1->0) | on request |
Relay power supply | by UP process voltage |
Relay outputs | |
output short-circuit protection | should be provided externally with a fuse or circuit breaker |
rated protection fuse | 6 A gL/gG per channel |
Output switching capacity | |
resistive load, max. | 3 A; 3 A (230 V AC), 2 A (24 V DC) |
inductive load, max. | 1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC) |
lamp load | 60 W (230 V AC), 10 W (24 V DC) |
Output switching capacity (XC version above 60 °C) | On Request |
Life time (cycles) | mechanical: 300 000; under load: 300 000 (24 V DC at 2 A), 200 000 (120 V AC at 2 A), 100 000 (230 V AC at 3 A) |
Spark suppression with inductive AC load | must be performed externally according to driven load specifications |
Demagnetization with inductive DC load | a free-wheeling diode must be circuited in parallel to the inductive load |
Switching frequency | |
with resistive load | max. 10 Hz |
with inductive load | max. 2 Hz |
with lamp load | max. xx Hz |
Max. cable length | |
shielded | 1000 m |
unshielded | 600 m |