Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…7

Nr. Name Value Internal value Internal value, type Default Min. Max. EDS Slot/Index
1 Module ID Internal

1210

*1)

Word

1210

0x04BA

0 65535 0x0Y01

2

*2)

Ignore module

No

Yes

0

1

Byte

No

0x00

    not for FBP
3 Parameter length Internal 5 Byte

5-CPU

4-FBP

0 255 0x0Y02
4 Check supply

Off

on

0

1

Byte

On

0x01

0 1 0x0Y03
5 Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

Byte

8 ms

0x02

0 3 0x0Y04

6

*4)

Fast Counter

0

:

10 *3)

0

:

10

Byte

Mode 0

0x00

    not for FBP
7 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05
8

Substitute value at outputs)

Bit 7 = Output 7

Bit 0 = Output 0

0…

255

0…

0xff

Byte

0

0x00

0 255 0x0Y06

*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

*3) Counter operating modes Fast Counter, see description of the Fast Counter Fast Counter

*4) With FBP and without the parameter Fast Counter

Note

The Fast Counter of the module does not work if the module is connected to an FBP Interface Module or CS31 Bus Module.

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const

  1. =

7

0x04, 0xbb, 0x04, \

0x01, 0x02, 0x00, 0x00;