Serial Interface COM2 of the Terminal Bases (PM57x, PM58x and PM59x)¶
Note
Processor Modules with type designator -2ETH (e. g. PM591-2ETH) do not have a COM2 interface.
The serial interface COM2 is connected via a 9-pole SUB-D plug. It is not intended to use COM2 to establish a CS31 system bus. It is configurable for RS-232 or RS-485 and can be used for
- online access
- a free protocol
- Modbus RTU, client and server
If the RS-485 bus is used, each interconnected bus line (each bus segment) must be electrically terminated. The following is necessary:
- 2 resistors of 120 Ohms each at both line ends (to avoid signal reflections)
- a pull-up resistor at RxD/TxD-P and a pull-down resistor at RxD/TxD-N. These 2 resistors care for a defined high level on the bus, while there is no data exchange.
It is useful, to activate both the pull-up and the pull-down resistors, which only are necessary once on every bus line, at the bus master.
Serial Interface | Pin | ||||
---|---|---|---|---|---|
1 | FE | Functional earth | |||
2 | TxD | RS-232 | Transmit data | Output | |
3 | RxD/TxD-P | RS-485 | Receive/Transmit | Positive | |
4 | RTS | RS-232 | Request to send | Output | |
5 | SGND | Signal ground | 0 V supply out | ||
6 | +5 V | 5 V supply out | |||
7 | RxD | RS-232 | Receive data | Input | |
8 | RxD/TxD-N | RS-485 | Receive/Transmit | Negative | |
9 | CTS | RS-232 | Clear to send | Input | |
Shield | FE | Functional earth |
Attention
:strong:Risk of corrosion!
Unused connectors and slots may corrode, if using XC devices in salt mist environments.
Protect unused connectors and slots with TA535 protective caps for XC devices TA535: Protective Caps TA535 for XC Devices Protective Caps TA535 for XC Devices.
The following drawing shows an RS-485 bus with the bus master at the line end.
RS-485 bus, master at a line end
If the master is located within the bus line, it does not need a terminating resistor. The pull-up and the pull-down resistors, however, are necessary:
RS-485 bus, master within the bus line
Attention
If the bus is operated with several masters, the pull-up and pull-down resistors may only be installed at one master.
The cable shields must be earthed. See CS31 System Bus CS31 System Bus.