CM572-DP PROFIBUS DP Communication Module FDL DDLM Requests Class 1

../_images/da324d51460074e40a33139000eba54e

Services, which were send continuously according to the PROFIBUS® DP standard, are counted in this table. Fundamentally, only the data-exchange-all should be count in a faultless network.

The services:

  • set-slave-list,
  • set-prm,
  • chk-cfg,
  • data-exchange,

permit in case of faultless course for each configured Slave module to be activated only 1 time. If the count changes continuously in case of these services, a bus error has occurred. If, for example the service slave-diag changes sporadically, the bus cable can have a defect, or the terminating resistor is missing in the cable. It is also possible, that a conscious error report of a Slave module activates the service in the Master.

Parameter Description
Set bus parameter Counter for Set-Bus-Par request
Set slave address list Counter for Set-Slave-List request
Slave diagnostic request Counter for Slave-Diag request
Check configuration request Counter for Check-Cfg request
Data exchange request Counter for Data-Exchange request
Data exchange conf. pos. Counter for Data-Exchange confirmation positive
Data exchange conf. neg. Counter for Data-Exchange confirmation negative
Data exchange all request Counter for Data-Exchange-All request
Data exchange all conf. pos. Counter for positive confirmation of Data-Exchange-All
Data exchange all conf. neg. Counter for negative confirmation of Data-Exchange-All