LED Status Display¶
The LEDs are located at the front of module. There are 2 different groups:
- The 5 system LEDs (PWR, NET, DC, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
- The 27 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs
LED | Color | off | on | flashing | 1x flash | 2x flash |
---|---|---|---|---|---|---|
PWR/RUN | green | Error in the internal supply voltage or process voltage missing | Internal supply voltage OK | Module is not configured | – | – |
yellow | – | – | – | – | – | |
NET | green | Init | operational | pre-operational | safe-operational | – |
red | No Error | PDI Watchdog Timeout | Invalid Configuration | Unsolicited State Change | Application time out | |
DC *) | green | Distributed Clock not active | Distributed Clock active | – | – | – |
red | – | – | – | – | – | |
S-ERR | red | No error | Internal error | – | – | – |
I/O-Bus | green | No expansion modules connected or communication error | — | — | – | – |
ETH1 | green | No EtherCAT® connection | Link OK No data transfer |
Link OK Data transfer OK |
– | – |
yellow | – | – | – | – | – | |
ETH2 | green | No EtherCAT® connection | Link OK No data transfer |
Link OK Data transfer OK |
– | – |
yellow | – | – | – | – | – |
*) The status of this LED is only significant if the camswitch functionality is enabled
Status of the 27 process LEDs
LED | Color | OFF | ON | Flashing |
---|---|---|---|---|
AI0 to AI3 | yellow | Input is OFF | Input is ON (brightness depends on the value of the analog signal) | – |
AO0 to AO1 | yellow | Output is OFF | Output is ON (brightness depends on the value of the analog signal) | – |
DI0 to DI7 | yellow | Input is OFF | Input is ON (the input voltage is even displayed if the supply voltage is OFF) | – |
DO0 toDO7 | yellow | Output is OFF | Output is ON | – |
UP | green | Process supply voltage missing | Process supply voltage OK and initialization finished | – |
UP3 | green | Process supply voltage missing | Process supply voltage OK | – |
CH-ERR1 to CH-ERR3 | red | No error or process supply voltage missing | Internal error | Error on one channel of the corresponding group |