Technical Data of the Module

Process supply voltage UP/UP3  
  Rated value 24 V DC (for inputs and outputs)
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP/UP3 10 A fast
  Electrical isolation Ethernet interface against the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.2 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections

Terminals 1.8 and 2.8 for +24 V (UP)

Terminal 3.8 for +24 V (UP3)

Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Diagnose See Diagnosis and Displays EtherCATâ Bus Module CI511-ETHCAT
Operation and error displays 32 LEDs (totally)
Weight (without Terminal Unit) ca. 125 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.