Connection of resistance thermometers in 2-wire configuration¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module CI511-ETHCAT provides a constant current source which is multiplexed over the max. 4 analog input channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration.
Connection of resistance thermometers in 2-wire configuration
The following measuring ranges can be configured EtherCATâ Bus Module CI511-ETHCAT EtherCATâ Bus Module CI511-ETHCAT:
Pt100 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Pt1000 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Ni1000 | -50 °C…+150 °C | 2-wire configuration, 1 channel used |
The function of the LEDs is described under Diagnosis and Displays / Displays EtherCATâ Bus Module CI511-ETHCAT.
The module CI511-ETHCAT performs a linearization of the resistance characteristic.
In order to avoid error messages from unused analog input channels, it is useful to configure them as “unused”.