Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply¶
The following figure shows the connection of active-type sensors (voltage) with no electrically isolated power supply.
Connection of active-type sensors (voltage) with no electrically isolated power supply
Caution
The minus pole at the sensors must not have a too big potential difference with respect to ZP (max. ± 1 V within the full signal range). Otherwise problems can occur concerning the common-mode input voltages of the involved analog inputs. Measurement faults will be caused.
The following measuring ranges can be configured EtherCATâ Bus Module CI511-ETHCAT EtherCATâ Bus Module CI511-ETHCAT:
Voltage | 0…10 V | 1 channel used |
Voltage | -10 V…+10 V *) | 1 channel used |
*) if the sensor can provide this signal range
The function of the LEDs is described under Diagnosis and Displays / Displays EtherCATâ Bus Module CI511-ETHCAT.
In order to avoid error messages or long processing times, it is useful to configure unused analog input channels as “unused”.