Connection of active-type analog sensors (voltage) with electrically \ isolated power supply¶
The following figure shows the connection of active-type analog sensors (voltage) with electrically isolated power supply
Connection of active-type analog sensors (voltage) with electrically isolated power supply
The following measuring ranges can be configured EtherCATâ Bus Module CI511-ETHCAT EtherCATâ Bus Module CI511-ETHCAT:
| Voltage | 0…10 V | 1 channel used | 
| Voltage | -10 V…+10 V | 1 channel used | 
The function of the LEDs is described under Diagnosis and Displays / Displays EtherCATâ Bus Module CI511-ETHCAT.
In order to avoid error messages or long processing times, it is useful to configure unused analog input channels as “unused”.