Technical Data of the Digital OutputsΒΆ
Number of channels per module | 16 normally-open relay outputs |
Distribution of the channels into groups | 2 (8 channels per group) |
Connection of the channels NO0 to NO7 | Terminals 1 to 8 |
Connection of the channels NO8 to NO15 | Terminals 10 to 17 |
Reference potential for the channels NO0 to NO7 | Terminal 9 (signal name R0..7) |
Reference potential for the channels NO8 to NO15 | Terminal 18 (signal name R8..15) |
Relay coil power supply | Terminals 19 and 20 (signal names L+ and M) |
Indication of the output signals | 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered through the I/O-Bus |
Way of operation | Non-latching type |
Relay output voltage | |
Rated value | 24 V DC or 120/240 V AC |
Output delay | |
Switching 0 to 1 (max.) | Typ. 10 ms |
Switching 1 to 0 (max.) | Typ. 10 ms |
Output current | |
Rated current per channel (max.) | 2.0 A (24 V DC / 120 V AC / 240 V AC, only resistive loads) 2.0 A (120 V AC, only pilot duty) 1.5 A (240 V AC, only pilot duty) |
Rated current per group (max.) | 10 A |
Lamp load (max.) | 200 W (230 V AC), 30 W (24 V DC) |
Spark suppression with inductive AC loads | Must be performed externally according to driven load specification |
Switching Frequencies | |
With resistive loads | Max. 1 Hz |
With inductive loads | On Request |
With lamp loads | Max. 1 Hz |
Short circuit / Overload proof | No, should be provided by an external fuse or circuit breaker |
Rated protection fuse (for each channel) | 5 A fast |
Overload message | No |
Output current limitation | No |
Connection of 2 outputs in parallel | Not possible |
Life time of relay contacts (cycles) | 100,000 at rated load |
Max. cable length | |
Shielded | 500 m |
Unshielded | 150 m |