Technical Data of the Digital OutputsΒΆ
| Number of channels per module | 16 normally-open relay outputs |
| Distribution of the channels into groups | 2 (8 channels per group) |
| Connection of the channels NO0 to NO7 | Terminals 1 to 8 |
| Connection of the channels NO8 to NO15 | Terminals 10 to 17 |
| Reference potential for the channels NO0 to NO7 | Terminal 9 (signal name R0..7) |
| Reference potential for the channels NO8 to NO15 | Terminal 18 (signal name R8..15) |
| Relay coil power supply | Terminals 19 and 20 (signal names L+ and M) |
| Indication of the output signals | 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered through the I/O-Bus |
| Way of operation | Non-latching type |
| Relay output voltage | |
| Rated value | 24 V DC or 120/240 V AC |
| Output delay | |
| Switching 0 to 1 (max.) | Typ. 10 ms |
| Switching 1 to 0 (max.) | Typ. 10 ms |
| Output current | |
| Rated current per channel (max.) | 2.0 A (24 V DC / 120 V AC / 240 V AC, only resistive loads) 2.0 A (120 V AC, only pilot duty) 1.5 A (240 V AC, only pilot duty) |
| Rated current per group (max.) | 10 A |
| Lamp load (max.) | 200 W (230 V AC), 30 W (24 V DC) |
| Spark suppression with inductive AC loads | Must be performed externally according to driven load specification |
| Switching Frequencies | |
| With resistive loads | Max. 1 Hz |
| With inductive loads | On Request |
| With lamp loads | Max. 1 Hz |
| Short circuit / Overload proof | No, should be provided by an external fuse or circuit breaker |
| Rated protection fuse (for each channel) | 5 A fast |
| Overload message | No |
| Output current limitation | No |
| Connection of 2 outputs in parallel | Not possible |
| Life time of relay contacts (cycles) | 100,000 at rated load |
| Max. cable length | |
| Shielded | 500 m |
| Unshielded | 150 m |