Technical Data of the Analog Outputs

Number of channels per module 8, all channels for voltage, the first 4 channels also for current
Distribution of channels into groups 1 group of 8 channels
  Channels O0-…O7- Terminals 3.0…3.7
  Channels O0+…O7+ Terminals 4.0…4.7
Output type bipolar with voltage, unipolar with current
Electrical isolation against internal supply and other modules
Configurability -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually), current outputs only channels 0…3

Output resistance (load),

as current output

0…500 W

Output loadability,

as voltage output

max. ±10 mA
Indication of the output signals one LED per channel
Resolution 12 bits (+ sign)
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range

typ. 0.5 %, max. 1 %

For XC version below 0 °C and above 60 °C: on request

Relationship between output signal and hex code table Analog Input/Output Module AX522
Unused outputs can be left open-circuited