Technical \ Data of the Analog Inputs¶
Number of channels per module | 8 |
Distribution of channels into groups | 1 group of 8 channels |
Connections of the channels I0- to I7- | Terminals 1.0 to 1.7 |
Connections of the channels I0+ to I7+ | Terminals 2.0 to 2.3 |
Input type | bipolar (not with current or Pt100/Pt1000/Ni1000) |
Electrical isolation | against internal supply and other modules |
Configurability | 0…10 V, -10…+10 V, 0/4…20 mA, Pt100/1000, Ni1000 (each input can be configured individually) |
Channel input resistance | Voltage: > 100 kΩ, current: ca. 330 Ω |
Time constant of the input filter | Voltage: 100 µs, current: 100 µs |
Indication of the input signals | one LED per channel |
Conversion cycle | 2 ms (for 8 inputs + 8 outputs), with Pt/Ni… 1 s |
Resolution | Range 0…10 V: 12 bits Range -10…+10 V: 12 bits + sign Range 0…20 mA: 12 bits Range 4…20 mA: 12 bits |
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | typ. 0.5 %, max. 1 % For XC version below 0 °C and above 60 °C: on request |
Relationship between input signal and hex code | tables Input ranges voltage, current and digital input Analog Input/Output Module AX522 and Input ranges resistance Analog Input/Output Module AX522 |
Unused voltage inputs | are configured as “unused” |
Unused current inputs | have a low resistance, can be left open-circuited |
Overvoltage protection | yes |