Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module slot address: Y = 1…7

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.

EDS

Slot/Index

1 Module ID Internal

1500

*1)

Word

1500

0x05dc

0 65535 0x0Y01

2

*2)

Ignore module

No

Yes

0

1

Byte

No

0x00

    not for FBP
3 Parameter length in bytes Internal 37 Byte

37-CPU

37-FBP

0 255 0x0Y02
4 Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
5 Analog data format Default 0 Byte

Default

0x00

    0x0Y04
6 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05
7

Channel configuration

Input channel 0

see table

Channel configuration

Byte

Default

0x00

0 19 0x0Y06
8

Channel monitoring

Input channel 0

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y07

9

to

22

Channel configuration and channel monitoring of the input channels 1 to 7

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

19

3

0x0Y08

to

0x0Y15

23

Channel configuration

Output channel 0

see table

Channel configuration

Byte

Default

0x00

0 130 0x0Y16
24

Channel monitoring

Output channel 0

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y17
25

Substitute value

Output channel 0

only valid for output channel 0 0…0xffff Word

Default

0x0000

0 65535 0x0Y18
26 to 31 Channel configuration and channel monitoring of the output channels 1 to 3

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y19

to

0x0Y1E

32

Channel configuration

Output channel 4

see table

Channel configuration

Byte

Default

0x00

0 128 0x0Y1F
33

Channel monitoring

Output channel 4

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y20

34

to

39

Channel configuration and channel monitoring of the output channels 5 to 7

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

128

3

0x0Y21

to

0x0Y26

*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

GSD file:

AX522

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

40

0x05, 0xdd, 0x25, \

0x01, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Input channel (8x):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *2) see below *2) Byte

0

0x00 see below *3)

   
2 Channel monitoring see below *4) see below *4) Byte

0

0x00 see below *5)

   

- Channel configuration

*2) Internal value Operating modes of the analog inputs, individually configurable
*3) 0 Unused (default)
  1 Analog input 0…10 V
  2 Digital input
  3 Analog input 0…20 mA
  4 Analog input 4…20 mA
  5 Analog input -10 V…+10 V
  8 Analog input Pt100, -50 °C…+400 °C (2-wire)
  9 Analog input Pt100, -50 °C…+400 °C (3-wire), requires 2 channels *)
  10 Analog input 0…10 V via differential inputs, requires 2 channels *)
  11 Analog input -10 V…+10 V via differential inputs, requires 2 channels *)
  14 Analog input Pt100, -50 °C…+70 °C (2-wire)
  15 Analog input Pt100, -50 °C…+70 °C (3-wire), requires 2 channels *)
  16 Analog input Pt1000, -50 °C…+400 °C (2-wire)
  17 Analog input Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels *)
  18 Analog input Ni1000, -50 °C…+150 °C (2-wire)
  19 Analog input Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels *)
    *) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).

- Channel monitoring

*4) Internal value Monitoring
*5) 0 Plausibility, open-circuit (broken wire) and short-circuit
  3 No monitoring

Output channel 0 (1 channel):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *6) see below *6) Byte see below *7)    
2 Channel monitoring see below *8) see below *8) Byte see below *9)    
3

Substitute value

*10)

0…65535 0… Word 0    

Output channels 1…7 (7 channels):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *6) see below *6) Byte see below *7)    
2 Channel monitoring see below *8) see below *8) Byte see below *9)    

- Channel configuration

*6) Internal value Operating modes of the analog outputs, individually configurable
*7) 0 Unused (default)
  128 Analog output -10 V…+10 V
  129 Analog output 0…20 mA (not with the channels 4…7 and 12…15)
  130 Analog output 4…20 mA (not with the channels 4…7 and 12…15)

- Channel monitoring

*8) Internal value Monitoring
*9) 0 Plausibility, open-circuit (broken wire) and short-circuit (default)
  3 No monitoring

- Substitute value

*10) Intended behaviour of output channel when the control system stops: Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
  Output OFF Off 0
  Last value infinite Last value 0
  Last value for 5 s and then turn off Last value 5 sec 0
  Last value for 10 s and then turn off Last value 10 sec 0
  Substitute value infinite Substitute value depending on configuration
  Substitute value for 5 s and then turn off Substitute value 5 sec depending on configuration
  Substitute value for 10 s and then turn off Substitute value 10 sec depending on configuration