Functionality¶
8 analog inputs, individually configurable for | unused (default setting) |
0…10 V | |
-10 V…+10 V | |
0…20 mA | |
4…20 mA | |
Pt100, -50 °C…+400 °C (2-wire) | |
Pt100, -50 °C…+400 °C (3-wire), requires 2 channels | |
Pt100, -50 °C…+70 °C (2-wire) | |
Pt100, -50 °C…+70 °C (3-wire), requires 2 channels | |
Pt1000, -50 °C…+400 °C (2-wire) | |
Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels | |
Ni1000, -50 °C…+150 °C (2-wire) | |
Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels | |
0…10 V with differential inputs, requires 2 channels | |
-10 V…+10 V with differential inputs, requires 2 channels | |
digital signals (digital input) |
4 analog outputs, individually configurable for | unused (default setting) |
-10 V…+10 V | |
0…20 mA | |
4…20 mA | |
4 analog outputs, individually configurable for | unused (default setting) |
-10 V…+10 V |
Resolution of the analog channels | |
- Voltage -10 V… +10 V | 12 bits plus sign |
- Voltage 0…10 V | 12 bits |
- Current 0…20 mA, 4…20 mA | 12 bits |
- Temperature | 0.1 °C |
LED displays | 19 LEDs for signals and error messages |
Internal power supply | through the expansion bus interface (I/O-Bus) |
External power supply | via the terminals ZP and UP (process voltage 24 V DC) |