Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process voltage  
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value 24 V DC
max. ripple 5 %
Protection against reversed voltage yes
Rated protection fuse on UP 10 A fast
Electrical isolation Yes, per module
Current consumption  
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module Ca. 2 mA
From UP at normal operation / with outputs 0.15 A + output loads
Inrush current from UP (at power up) 0.050 A:sup:2s
Max. length of analog cables, conductor cross section > 0.14 mm² 100 m
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range

Typ. 0.5 %, max. 1 %

For XC version below 0 °C and above 60 °C: on request

Weight 300 g
Mounting position

Horizontal

or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.