Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module AI523: Module slot address: Y = 1…7

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.

EDS

Slot/Index

1 Module ID Internal

1515

*1)

Word 1515 0x05eb 0 65535 0x0Y01

2

*2)

Ignore module

No

Yes

0

1

Byte

No

0x00

    not for FBP
3 Parameter length in bytes Internal 34 Byte

34-CPU

34-FBP

0 255 0x0Y02
4 Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
5 Analog data format Default 0 Byte

Default

0x00

    0x0Y04
6

Channel configuration

Input channel 0

see table

Channel configuration

Byte

Default

0x00

0 19 0x0Y05
7

Channel monitoring

Input channel 0

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y06

8

to

35

Channel configuration and channel monitoring of the input channels 1 to 14

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

19

3

0x0Y07

to

0x0Y22

36

Channel configuration

Input channel 15

see table

Channel configuration

Byte

Default

0x00

0 19 0x0Y23
37

Channel monitoring

Input channel 15

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y24

*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

GSD file:

AI523

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

37

0x05, 0xec, 0x22, \

0x01, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Input channel (16 x with AI523):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *2) see below *2) Byte

0

0x00 see below *3)

   
2 Channel monitoring see below *4) see below *4) Byte

0

0x00 see below *5)

   

- Channel configuration

*2) Internal value Operating modes of the analog inputs, individually configurable
*3) 0 Unused (default)
  1 Analog input 0…10 V
  2 Digital input
  3 Analog input 0…20 mA
  4 Analog input 4…20 mA
  5 Analog input -10 V…+10 V
  8 Analog input Pt100, -50 °C…+400 °C (2-wire)
  9 Analog input Pt100, -50 °C…+400 °C (3-wire), requires 2 channels *)
  10 Analog input 0…10 V via differential inputs, requires 2 channels *)
  11 Analog input -10 V…+10 V via differential inputs, requires 2 channels *)
  14 Analog input Pt100, -50 °C…+70 °C (2-wire)
  15 Analog input Pt100, -50 °C…+70 °C (3-wire), requires 2 channels *)
  16 Analog input Pt1000, -50 °C…+400 °C (2-wire)
  17 Analog input Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels *)
  18 Analog input Ni1000, -50 °C…+150 °C (2-wire)
  19 Analog input Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels *)
    *) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).

- Channel monitoring

*4) Internal value Monitoring
*5) 0 Plausibility, open-circuit (broken wire) and short-circuit
  1 Open-circuit and short-circuit
  2 Plausibility
  3 No monitoring