Technical Data of the Digital Inputs

Number of channels per module 8 AC inputs (100-240 V AC)
Distribution of the channels into groups 8 (1 channel per group)
Input voltage range 0..264 V AC (47 … 63 Hz)
Input current per channel (typically at 25 °C)

<5 mA (at 40 V AC)

>6 mA (at 159 V AC, 50 Hz)

>7 mA (at 159 V AC, 60 Hz)

Connections of the channels I0 to I7 Terminals 1, 3, 5, 7, 10, 12, 14, 16
Reference potential for the channels I0 to I7 Terminals 2, 4, 6, 8, 11, 13, 15, 17
Indication of the input signals 1 yellow LED per channel; the LED is ON when the input signal is high (signal 1)
Input type according to EN 61131-2 Type 1
Input signal range  
  Signal 0 (max.) 20 V AC
  Undefined signal 20 V AC < U < 79 V AC
  Signal 1 (min.) 79 V AC
Input delay  
  signal 0 -> 1 Typ. 15 ms
  signal 1 -> 0 Typ. 30 ms
Max. permissible leakage current (at 2-wire proximity switches) 1 mA
Max. cable length  
  Shielded 500 m
  Unshielded 300 m