Dial-up Configuration of the CM574-RCOM Communication Module¶
Note
ABB recommends HSM Eco Modems for usage with CM574-RCOM Communication Modules.
In order to use dial-up connections, a modem module has to be appended to the RCOM/RCOM+ Communication Module in the project structure:
The module contains several parameters to configure the modem configuration.
The module contains all commands required for controlling the modem. It is preconfigured for the Logem LGH 9600H1 modem and should not be changed if using these modems.
The parameters shown in the “Module parameters” tab have the following meaning:
Parameter | Default value | Value | Meaning |
---|---|---|---|
Modem init | ATZ^M~~ATI4^M~ | String | Hayes compatible AT command to initialize connected modem. |
Dial prefix 1…6 | ATDT | String | Hayes compatible AT command to dial a number. 6 different dial prefixes can be configured. |
Dial suffix | ^M | String | Hayes compatible AT command string that is appended to the dial string. |
Connect answer | CONNECT | String | Message of the connected modem, if connection is established. |
Modem ring | RING | String | Message of the connected modem, if incoming call is registered. |
No carrier | NO CARRIER | String | String Message of the connected modem, if no carrier is detected. |
Command mode | ~~+++~~ | String | Hayes compatible AT command to switch modem to command mode. |
Modem answer | ATA^M | String | Hayes compatible AT command to answer incoming call. |
Modem hangup | ATA^M~~~~~ | String | Hayes compatible AT command to hang up (terminate) an existing connection. |
Max ring time | 70 | 0…255 | Maximum time [s] until a call is cancelled. |
Max number of calls | 3 | 0…255 | Maximum number of calls executed to establish a connection to a communication partner. |
Call delay | 2 | 0…255 | Delay time [s] between two calls. |
Hangup time | 30 | 0…255 | Time until a hang up process is considered as completed. |
After configuring the modem, a list of telephone numbers (phone book) has to be created for the nodes of the RCOM network. This is done by adding new sub entries to the “Dial-up modem” entry.
The telephone numbers can be assigned to the different nodes of the network by entering the corresponding address in the “Base parameters” tab.
Parameter | Default value | Value | Meaning |
---|---|---|---|
Node id | 0 | 0…254 | The node number (address) of the RCOM partner (read-only). |
To configure the telephone number, the following parameters have to be defined in the “Module parameters” tab:
Parameter | Default value | Value | Meaning |
---|---|---|---|
Dial prefix number | 1 | 1…6 | Identifier for the corresponding prefix. Prefixes can be configured under module “Dial-up modem” as described above. |
Telephone number | - | Valid telephone number | The telephone number as a string |