Dial-up Configuration of the CM574-RCOM Communication Module

Note

ABB recommends HSM Eco Modems for usage with CM574-RCOM Communication Modules.

In order to use dial-up connections, a modem module has to be appended to the RCOM/RCOM+ Communication Module in the project structure:

../_images/3862afcecbc4e41c0a33139001ca7e3d

The module contains several parameters to configure the modem configuration.

../_images/fc370918cbc4ed120a3313900136af3e

The module contains all commands required for controlling the modem. It is preconfigured for the Logem LGH 9600H1 modem and should not be changed if using these modems.

The parameters shown in the “Module parameters” tab have the following meaning:

Parameter Default value Value Meaning
Modem init ATZ^M~~ATI4^M~ String Hayes compatible AT command to initialize connected modem.
Dial prefix 1…6 ATDT String Hayes compatible AT command to dial a number. 6 different dial prefixes can be configured.
Dial suffix ^M String Hayes compatible AT command string that is appended to the dial string.
Connect answer CONNECT String Message of the connected modem, if connection is established.
Modem ring RING String Message of the connected modem, if incoming call is registered.
No carrier NO CARRIER String String Message of the connected modem, if no carrier is detected.
Command mode ~~+++~~ String Hayes compatible AT command to switch modem to command mode.
Modem answer ATA^M String Hayes compatible AT command to answer incoming call.
Modem hangup ATA^M~~~~~ String Hayes compatible AT command to hang up (terminate) an existing connection.
Max ring time 70 0…255 Maximum time [s] until a call is cancelled.
Max number of calls 3 0…255 Maximum number of calls executed to establish a connection to a communication partner.
Call delay 2 0…255 Delay time [s] between two calls.
Hangup time 30 0…255 Time until a hang up process is considered as completed.

After configuring the modem, a list of telephone numbers (phone book) has to be created for the nodes of the RCOM network. This is done by adding new sub entries to the “Dial-up modem” entry.

../_images/ec5a981fcbc4e7570a331390014c1538

The telephone numbers can be assigned to the different nodes of the network by entering the corresponding address in the “Base parameters” tab.

../_images/1f455930cbc4ef910a33139001ffb37e
Parameter Default value Value Meaning
Node id 0 0…254 The node number (address) of the RCOM partner (read-only).

To configure the telephone number, the following parameters have to be defined in the “Module parameters” tab:

../_images/b0a71ce0cbc4f27e0a331390006351e9
Parameter Default value Value Meaning
Dial prefix number 1 1…6 Identifier for the corresponding prefix. Prefixes can be configured under module “Dial-up modem” as described above.
Telephone number - Valid telephone number The telephone number as a string